Air-cooled BESS

For finding permanent and intermittent faults on live cables

Built on the EPCS125-AM power conversion system — European/Australian platform, grid-connected and off-grid capable.

 

Key specifications

3 ITEMS PENDING CONFIRMATION

Parameter EPCS125-AM-(F)
DC SIDE
Operating voltage range 615–950 V
Maximum current 203 A
AC SIDE – GRID-CONNECTED
Rated voltage 230/400 V, 3W+PE or 3W+N+PE
Rated output power 125 kW PENDING – brochure states 105 kW
Maximum apparent power 138 kVA
Rated frequency 50/60 Hz (±5)
Current distortion <2% at rated power
Overload capability 110% continuous (rated conditions)
Maximum efficiency 98.5% PENDING – brochure states 88%
AC SIDE – OFF-GRID
Rated output voltage 230/400 V
Voltage harmonics <3% (linear load)
SYSTEM
Usable capacity range Up to 241 kWh PENDING – datasheet suggests 261 kWh
Cooling Intelligent forced-air
Operating temperature −30 °C to 55 °C (derating above 45 °C)
Altitude 4000 m (derating above 2000 m)
Protection functions AC overcurrent / overvoltage / short-circuit, anti-islanding, DC reverse-polarity

Figures marked pending are under confirmation with our engineering team following a brochure/datasheet reconciliation; the published site will carry the confirmed set only. Certification listings are deliberately limited to completed type tests.

Need help choosing the right solution?

Our engineers can guide you.