T-305-16 High Voltage Surge Generator

The T-305-16 high voltage surge generator, is used for locating high impedance and flashing faults on distribution cables. It works in conjunction with a cable fault locator for pre-locating the fault position and then with a pinpointer to find the precise fault location.  It is applicable for different cable fault location techniques, such as the impulse current method (ICM) and the secondary/multiple impulse method (SIM/MIM).

(Top view of the control panel)

The equipment consists of a capacitor bank, an in-built voltage transformer and a rectifier, switchable to achieve different capacitance and voltage levels. When the unit is switched-off, its automatic and manual discharge facilities removes any residual capacitive charge. These features, together with safety interlocking, ensure safe, reliable and easy-to-use operation.

The T-305-16 also provides repetitive discharges to facilitate pinpointing through the detection of the magnetic field and audio signals related to the fault discharging.

Technical Data

Surge Voltage 0 – 32kV; 0 – 16kV; 0 – 8 kV
Surge Steps 8µF (0 – 16kV),  32µF (0 -8kV), 128µF (0 – 4kV)
Surge Energy 1024J per step
DC Test (kV)/mA 0…32kV / 48mA (1024J)
Negative polarity
Operating Modes Single pulse, Cyclic pulse, DC
Mode Of Operation DC / single impulse / multiple impulse
Discharge Period 4 – 15 s. Continuously adjustable
Testing Method ICM, SIM/MIM
Dimensions 500 x 400 x 960mm (1024J)
Weight 84kg
Operating Temperature -10 – +50oC
Operating Relative Humidity 20% – 90% relative humidity
Operating Atmospheric Pressure 86 – 106kPa
Ingress protection IP21 (IP54 with optional cover)

Mains Supply 220V ± 10% (110V available)
Mains Frequency 50/60Hz ± 20%
Maximum Power Consumption 1200W