T-907 Power Cable Fault Locator

Fault Pre-location

A power cable fault is unlikely to exhibit a sufficiently low resistance to allow a Time Domain Reflectometry (TDR) pulse to be reflected and it is usually necessary to modify the fault to create a situation where it is suitable for pre-location techniques to be applied. This is carried out using a surge generator to inject energy into the cable. This energy converts the fault such that the fault becomes low-resistance, allowing the use of TDR to measure the distance to the fault.

The TDR injects impulse on to cable and compares the reflection from the cable before and during the arcing. The deviation of the signals (D) represents the distance to the fault position based on time and a known pulse propagation velocity. This technique allows the approximate position of the fault to be determined. The exact location will then be identified through pinpointing.

T-907

The T-907 is a lightweight, portable fault locator for low, medium and high-voltage power cables, which can be applied for the pre-location of all kinds of faults, including open circuit, short circuit, low resistance, high-resistance and flashovers. The system utilises a separate, wireless display on a tablet computer, enhancing both the quality and safety of the system, while adding features such as communication of data and photography of site conditions.

The T-907 can operate in four modes: Time Domain Reflectometry (TDR), Secondary/Multiple Impulse Method, (SIM/MIM), Impulse Current Method (ICM) and the Decay Method. Most power cable faults exhibit a high resistance, which requires the application of a high voltage surge to break it down for the purpose of pre-location. Of the operating modes available, ICM is the most cost-effective method of producing a flashover at the fault point using a standard surge generator. In the T-907, the ICM is augmented by an Automatic Impulse Current (AIC) method, in which waveform recognition techniques are applied to calculate the fault location automatically, without the need for the operator to manually interpret the waveforms. For flashover faults requiring a high breakdown voltage, the Decay Method can be applied in conjunction with a HV DC source. The cable is charged by the DC source until it breaks down, creating a transient voltage signal which is captured through a capacitive voltage divider and used for fault location analysis.

T-907 technical data

Measuring range 64km
Fault location methods TDR, ICM, SIM/MIM and Decay
Voltage of transmitting pulse 30V
Width of transmitting pulse 40ns -7μs
Voltage withstand 400V AC (50/60Hz)
Output impedance 5-87Ω
Sampling rate 400MHz (2.5ns)
Display  Independent wirelessly connected 8” tablet
Charger (Main unit) Input: 110V – 240V AC; Output 8.4V DC, Current 3A
Charger (Tablet) Input: 100V – 240V AC; Output 5V DC, Current 3A
Weight (Main unit) 2.8kg
Weight (Tablet) >1kg
Dimensions (Main unit) 270 x 250 x 120mm
Dimensions (Tablet) 2270 x 140 x 18mm
Operating temperature -10o to +50oC
Ingress protection IP54: Splash proof and dust protected (when closed)
Storage temperature -20 to +50°C

Our products:
Distribution Automation – PZK-56 PZK-560K PZK-560Z
Power Utility – FTR-100 T-GPS XC-2100E 
Reluctance Motor – SRM/SRD SynRM